Model | CTS0030N | CTS0060N | CTS0080N | CTS0080N | ||
Cooling Capacity | kW | 3 | 6 | 8 | 8 | |
Power Consumption (35°C) | kW | 1.15 | 2.31 | 3.08 | 3.08 | |
EER (35°C) | / | 2.6 | 2.6 | 2.6 | 2.6 | |
Power Consumption (45°C) | kW | 1.36 | 2.86 | 3.64 | 3.64 | |
EER (45°C) | / | 2.2 | 2.1 | 2.2 | 2.2 | |
Rated Outlet Temperature | ºC | 18 | 18 | 18 | 18 | |
Electric Heating | kW | 2 | 2 | 2 | 2 | |
Pipe Diameter | / | NW26 | NW26 | NW26 | NW26 | |
Flow Rate | L/min | 40 | 50 | 50 | 60 | |
Head (Lift) | kPa | 80 | 80 | 80 | 80 | |
Refrigerant | / | R410A | R410A | R410A | R410A | |
Dimensions | Width | mm | 275 | 275 | 275 | 275 |
Depth | mm | 1100 | 1100 | 1100 | 1100 | |
Height | mm | 800 | 800 | 800 | 1050 | |
Unit Weight | kg | 80 | 95 | 95 | 115 | |
Power Supply | V/Hz | 220V/50Hz | 220V/50Hz | 220V/50Hz | 220V/50Hz | |
Operating Temperature Range | ºC | -30~55 | -30~55 | -30~55 | -30~55 | |
External Circulation Airflow Method | Forward Inlet and Rear Outlet | Forward Inlet and Rear Outlet | Forward Inlet and Rear Outlet | Forward Inlet and Rear Outlet | ||
Installation Method | Built-in Type | Built-in Type | Built-in Type | Built-in Type |
Cooltec Cooling Technology (Qingdao) Co., Ltd. is a high-tech enterprise integrating R&D, manufacturing, sales, and service. At present, the company's main products are industrial air conditioners and water chillers. The core R&D team of Coltec comes from a famous industrial refrigeration enterprise in the US and has world-leading industrial refrigeration technology.
1. What are the main benefits of using a liquid cooling solution for energy storage? |
Liquid cooling provides superior thermal management, enhancing the efficiency and lifespan of energy storage systems. It also helps optimize energy use and reduce the risk of overheating, ensuring the system operates at peak performance. |
2. How does the system handle high ambient temperatures? |
Our liquid cooling solution is designed with a wide operating temperature range from -30°C to 55°C, ensuring stable performance even in extreme environments. Additionally, the system features full-variable frequency design for efficient energy use under varying temperature conditions. |
3. What is the energy efficiency of the cooling solution? |
The system is highly energy-efficient, with an EER (Energy Efficiency Ratio) of up to 4.5 at 35°C and 3.8 at 45°C. This ensures minimal energy consumption while maintaining effective cooling performance. |
4. Is the system easy to install and maintain? |
Yes, the system has an integrated design that reduces on-site installation and commissioning costs. It also has self-diagnostic and protection functions, making maintenance simple and cost-effective over its 10+ year design life. |
5. Can the cooling system operate continuously 24/7? |
Yes, the cooling system is designed for continuous 24-hour operation, ensuring that your energy storage systems stay at optimal temperatures without interruptions. |
6. What types of communication interfaces are supported? |
The system comes standard with an RS485 communication interface, and we offer an optional CAN communication interface for seamless integration with your energy management system. |
7. Does the cooling solution require external power or heating support? |
The system is equipped with PTC heating to ensure reliable operation in low-temperature environments. The design also includes an integrated power supply for efficient operation. |
8. What refrigerants are used in the cooling system? |
Our system uses environmentally friendly refrigerants that comply with global environmental standards. Specific refrigerants can be discussed depending on the region and application. |
9. What is the protection rating of the cooling unit? |
The cooling unit has a protection rating of IPX5, meaning it is resistant to water and dust, making it suitable for both indoor and outdoor installations. |
10. What is the expected lifespan of the cooling system? |
The liquid cooling system is designed for a lifespan of over 10 years, with minimal maintenance required, offering long-term reliability and performance in industrial and commercial energy storage applications. |